Automatic capacitor banks with static contactor, wall-mounted , 50 Hz.

OPTIM EMS-C-31,25-440

OPTIM EMS-C-31,25-440, Capacitor bank

Code: R4A304.

  • Cable section (mm2): 1 x 16
  • Nr steps: 3
  • kvar (400 V): 26
  • kvar (440 V): 31,25
  • Man.Switch (A): Included
  • Composition: (6,25 + 2 x 12,5)
  • Use voltage (V): 440

INFORMATION

Description

Optim EMS-C capacitor banks are designed for power factor correction in networks with highly fluctuating load variations. Their switching system is based on the use of solid state semiconductors and it allows the different steps to be connected and disconnected in only milliseconds.

With this system, transients are prevented between the connection and disconnection of the steps, obtaining an immediate response to the load fluctuations. In addition, the need for maintenance of the capacitor bank is reduced thanks to the absence of moving elements.

Applications

The most common application is with individual loads or in installations where a quick compensation response is needed (for ex., welding units, motors for lifting units, lifts, etc.)

SPECIFICATIONS

AC power supply
Frequency
fn marcada en la etiqueta
Nominal voltage
Un marcada en la etiqueta
Electrical characteristics
Losses (W)
1 W/kvar
Discharge resistance
75 V / 3 min
Tolerance C
± 10%
Voltage
10 % (440 V for 400 V equipment)
Mechanical characteristics
Size (mm) width x height x depth
545 x 710 x 220 (mm)
Envelope
Exposi type with oven drying. RAL 7035 Grey / RAL 3005 Garnet
Ventilation
Natural outdoor ambient temperature ≤ 40 ºC. For outside ambient temperature > 40 ºC, the room where the battery is located must be cooled.
Weight (kg)
42
Environmental characteristics
Protection class
Marked on the label
Relative humidity (without condensation)
80%
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum during 1h: 55 ºC
Current measurement circuit
Allowable overload
1,3 In
Permanent overload
1,3 In
Transformation ratio
Transformer In/5 A
Standards
Electrical safety, Maximum height (m)
1000 máx.
Standards
UNE-EN 61921, UNE-EN 61642, IEC 60831
Protection
Element
Internal fuses and overpressure system
Circuit breaker type
Three-pole circuit breaker per step, curve C. Icc = 6 kA / 400 V

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Datasheet
Catalogue
CE-certified
Software & Firmware

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR