Automatic capacitor banks with static contactor, 50 Hz.

OPTIM EMK12-1200-440

OPTIM EMK12-1200-440, Static capacitor bank

Code: R46609.

  • Cable section (mm2): 2x240 / 2x240
  • kvar (400 V): 992
  • kvar (440 V): 1200
  • Optional circuit breaker (A) : 2x1000
  • Optional manual switch (A): 2x1000
  • Composition: 12x100
  • Use voltage (V): 440

INFORMATION

Description

The OPTIM-EMK-series capacitor banks have been designed for power factor correction in networks with fluctuating loads.

The power variations are relatively quick (measured in milliseconds) and the operation is thus carried out by thyristors, which are connected to a voltage controller board, so that the connection and disconnection of the capacitor is carried out with zero voltage difference.

Transients are prevented between the connection and disconnection of the steps, obtaining an immediate response to the load fluctuations.

Applications

The most common application is with individual loads or in installations where a quick compensation response is needed (for ex., welding units, motors for lifting units, lifts, etc.)

SPECIFICATIONS

Electrical characteristics
Discharge resistance
75 V / 3 min
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Reinforcement voltage
440 V (400 V)
Voltage
400 V (other voltages on request)
Mechanical characteristics
Size (mm) width x height x depth
2400 x 1900 x 650 (mm)
Fastening
Vertical. Minimum distance between condensers 2 cm
Ventilation
Natural or forced according to options
Weight (kg)
668
Environmental characteristics
Protection class
IP 21
Relative humidity (without condensation)
80%
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 50 ºC, minimum: -25 ºC
Standards
Certifications
VDE 560
Electrical safety, Maximum height (m)
2000
Standards
IEC 60831-1, IEC 70/7, UNE-EN 20827, UNE-EN 20010, BS 1650
Current measurement circuit
Allowable overload
1,3 In
Permanent overload
1,3 In
Features / performance
Components
Three-phase measurement CLZ capacitor Static switching unit at each step, comprising static contactors (thyristors) Individual protection at each step via fuses with high cut-off power (APR), NH-00 or Neosted Series according to type Two-pole circuit breaker protection for battery and regulator operation Max Fast computer series reactive energy regulator Radiators for heat dissipation Thermostat built into the radiator itself to disconnect the step in case of high temperature (90 ºC)
Optional
Manual circuit breaker at capacitor bank header Circuit breaker at capacitor bank header Circuit breaker + earth leakage protection at capacitor bank header Forced ventilation unit + thermostat Polycarbonate plate to avoid direct exposure 400/230 V autotransformer

DIMENSIÓN

VÍDEOS

DESCARGAS

User's manual
Dimensions