Automatic capacitor banks, 2.5 to 1600 kvar, 50 Hz.

OPTIM 14L P&P-1150-440

OPTIM 14L P&P-1150-440, Automatic capacitor bank

Code: R36L40.

  • Cable section (mm2): 3x185/2x150
  • Nr steps: 12
  • kvar (400 V): 950
  • kvar (440 V): 1150
  • Optional circuit breaker (A) : 1600+800
  • Optional manual switch (A): 1600+800
  • Composition: 50+11x100
  • Use voltage (V): 440
  • Mounting: Floor-mounted

INFORMATION

Description

The OPTIM P&P series automatic capacitor bank units have been designed for the automatic compensation of reactive energy in networks with fluctuating load levels and power variations during seconds, by switching operations carried out by contactors.

Applications

Their simple installation, high-technology and robustness make the OPTIM P&P series the ideal unit for compensating reactive energy in installations with fluctuating load levels.

SPECIFICATIONS

AC power supply
Frequency
50 Hz
Electrical characteristics
Voltage
404 V (other voltages on request)
Reinforcement voltage
440 V
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Manoeuvre voltage
Contactors: 230 V
Discharge resistance
75 V / 3 min
Tolerance C
-5% / 10 %
Losses (W)
< 0,5 W/kvar
Current measurement circuit
Permanent overload
1,3 In
Transformation ratio
In/5 A
Environmental characteristics
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 55 ºC, minimum: -50 ºC
Relative humidity (without condensation)
80%
Protection class
IP 21
Mechanical characteristics
Envelope
Sheet metal RAL 7035 Grey / RAL 3005 Garnet
Fastening
Vertical
Ventilation
Natural or forced according to options
Weight (kg)
495
Size (mm) width x height x depth
2100 x 1900 x 650 (mm)
Protection
Element
Fuses with high cut-off power (APR), type NH-00
Features / performance
Components
Reactive energy regulator, Computer C Wi-Fi, with digital indication and 6 or 12 relay outputs according to type.
Optional
Manual circuit breaker at capacitor bank header. Circuit breaker at capacitor bank header Circuit breaker + earth leakage protection at capacitor bank header. Forced ventilation unit + thermostat. Polycarbonate plate to avoid direct exposure. 400/230 V autotransformer (included in OPTIM 8, 9, 8L, 14L, and 16L) Regulator with built-in network analyser and three-phase Computer SMART III measurement. Other frequencies, consult.
Standards
Standards
IEC 60831-1, IEC 61921, IEC 60439
Electrical safety, Maximum height (m)
1000 máx. (para altitud mayor prever siempre ventilación forzada)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Dimensions
Datasheet
CE-certified
Video Installation
Software & Firmware
Catalogue
Leaflet

ACCESORIES