Individual protection of each step with fuses with high rupture power (HRP). NH-00 Series.
Features / performance
Components
CLZ capacitor (460 V)
Contactors with pre-insertion block and quick discharge resistor
Two-pole protection circuit-breaker for capacitor bank and regulator operations.
Power factor regulator of the Computer C Wi-Fi series.
Detuned filters tuned at 189 Hz (50 Hz) /227 Hz (60 Hz) for the protection against harmonics present in the network and to avoid the problems of
resonance with fifth or higher order harmonics.
Built-in thermostat for the disconnection of the step in case of excessive temperatures (90 ºC).
Auto-transformer.
Optional
Manual capacitor bank header switch
Automatic capacitor bank header switch
Automatic switch + Earth leakage protection at the capacitor bank’s header
Forced ventilation unit + thermostat
Polycarbonate plate to protect against direct contacts
Standards
Standards
IEC 60831-1, UNE 60831-1, IEC 61921, IEC 60439, IEC 61439