SPECIFICATIONS

Electrical characteristics
Voltage
400 V (50 Hz) (other voltages on request)
Reinforcement voltage
440 V
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Manoeuvre voltage
Contactors: 230 V
Discharge resistance
75 V / 3 min
Tolerance C
-5% / 10 %
Losses (W)
< 0,5 W/kvar
Current measurement circuit
Permanent overload
1,3 In
Transformation ratio
In / 5A
Environmental characteristics
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 55 ºC, minimum: -50 ºC
Relative humidity (without condensation)
80%
Protection class
IP 21
Mechanical characteristics
Envelope
Sheet metal RAL 7035 Grey / RAL 3005 Garnet
Fastening
Vertical / Self-supporting
Ventilation
Natural or forced according to options
Weight (kg)
108
Size (mm) width x height x depth
800 x 1200 x 500 (mm)
Protection
Element
Individual protection of each step with fuses with high rupture power (HRP). NH-00 Series.
Features / performance
Components
CLZ capacitor (460 V) Contactors with pre-insertion block and quick discharge resistor Two-pole protection circuit-breaker for capacitor bank and regulator operations. Power factor regulator of the computer Max series. Detuned filters tuned at 189 Hz (50 Hz) /227 Hz (60 Hz) for the protection against harmonics present in the network and to avoid the problems of resonance with fifth or higher order harmonics. Built-in thermostat for the disconnection of the step in case of excessive temperatures (90 ºC). Auto-transformer.
Optional
Manual capacitor bank header switch Automatic capacitor bank header switch Automatic switch + Earth leakage protection at the capacitor bank’s header Forced ventilation unit + thermostat Polycarbonate plate to protect against direct contacts
Standards
Standards
IEC 60831-1, UNE 60831-1, IEC 61921, IEC 60439, IEC 61439
Electrical safety, Maximum height (m)
2000 m

DIMENSIONS

CONNECTIONS