SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
2 W / 16 VA
Frequency
50 / 60 Hz
Nominal voltage
184 … 276 Vca (Autoalimentado)
Current measurement circuit
Installation category
CAT III 300 V
Phase current measuring range
0,1 … 3 A
Minimum current measurement
0,08 A
Voltage measurement circuit
Installation category
CAT III 300 V
Input impedance
600 MΩ
Voltage measuring range
184 … 276 Vac
Electrical characteristics
Insulation voltage, circuit
4 kV RMS 50 Hz durante 1 minuto
Standards
Standards
UNE-EN 61347-1/A1, UNE-EN 61347-2-12/A1, UNE-EN 60929, UNE-EN 61010-1, UNE-EN 61000-6-3/A1, UNE-EN 61000-6-2
Other digital relay outputs
Type
Control de doble nivel
Maximum current
5A
Maximum switching capacity
1250 VA - 150 W
Maximum open contact voltage
250Vca
Electrical life
1x105 ciclos
Mechanical life
2x107 cycles
Digital relay outputs
Type
Control ON/OFF
Maximum current
10A
Maximum open contact voltage
250 V ~
Electrical life
100x103ciclos
Mechanical life
10x106 cycles
Maximum switching capacity
2500 W (AC1)
Mechanical characteristics
Weight (kg)
0,28
Measurement accuracy
Phase current measurement
< 5% FS
Reactive power measurement (kvar)
< 5% F.S.
Active power measurement (kW)
< 5% F.S.

DIMENSIONS

CONNECTIONS

VIDEOS

CIRLAMP. Management system for street lights

DOWNLOADS

Datasheet
Catalogue
CE-certified
Product video

ACCESORIES