Advanced power quality analyzers (according Standard UNE-EN-50160 and IEC 61000-4-30)

QNA 600

QNA600, Advanced power quality analyzers

Code: Q22010.

  • Protocol: HTTPS - NTP - SFTP - IEC61850
  • Memory: 16 GB
  • Events / Waveform: Yes
  • Web server: Yes
  • Certification: IEC 61000-4-30 (Class A)
  • Energy accuracy: 0,5s
  • Communications: Ethernet | Wi-Fi | 4G
  • Harmonics: 64
  • Class: A
  • Measurement Range (V): 11 ... 500 V ~ (V F-N / V Ph-N)
  • Measurement Range (A): 0.05 ... 10 A
  • Power supply: 180 ... 300 V ~
  • Input current: ... / 5 A
  • Mounting: Rack

INFORMATION

Description

The QNA 600 is a high-end power quality analyzer that measures and records electrical parameters, power quality events and transient events in an electrical installation with maximum accuracy. This allows any incidents that said power quality events may have caused in the installation or on the devices connected to it to be analysed after the fact.

It complies with IEC 61000-4-30, edition 3, and IEC 62586-2. Its designation, PQI-A-FI1-H, defines it as a Class A device for fixed installation in 19" 4U racks, suitable for interiors with uncontrolled temperatures and noisy environments. It has 5 voltage and 5 current measurement channels, and is compatible with current transformers of up to 5 amperes.
The device has two Ethernet ports (front/rear), a simple API and protocols such as IEC 61850, MQTT, ftp and sftp for integration into SCADA applications, as well as to access instantaneous values and historical data, which can be downloaded in PQDIFF and COMTRADE formats.

It generates EN 50160 reports in PDF format automatically, and sends them to sftp or ftp repositories, providing the user with detailed information on the power quality. GPS synchronization ensures the accuracy of the time mark and location.
It also has an internal memory that records data for 5 years and can store up to 4,000 quality events, in standard configuration, for subsequent analysis.

Applications

The QNA 600 has been specially designed to be installed at utility demarcation points (transformer station) or at the main connection of any user's electrical installation, operating in parallel to the billing meter. This gives it the ability to automatically detect and analyse the utility's compliance with the EN 50160 standard, and it can also be used to identify power quality events that may cause damage, deterioration or malfunction in the installation loads.
This information allows the user to understand the effects of the problem and to take corrective measures if the quality problems are caused by the loads in the installation itself. Moreover, if the problems are caused by external factors, this device is IEC 61000-4-30 certified, and offers reliable data to demonstrate any incident or damage caused by the utility company.

SPECIFICATIONS

AC power supply
Nominal voltage
180 … 300 V ~
Frequency
50 … 60 Hz.
Consumption
15 … 25 VA
Installation category
CAT III 300 V
Auxiliary battery power supply
Battery type
Ni-MH
Capacity
2500 mAh
Autonomy
30 minutes
Voltage measurement circuit
Nominal voltage
230 V ~
Voltage measuring range
11 … 500V Ph-N / 17 … 866V Ph-Ph
Frequency measuring range
42.5 … 69 Hz
Input impedance
1 MΩ
Minimum measurement voltage (Vstart)
11 V ~
Installation category
CAT IV 600 V
Current measurement circuit
Nominal current (In)
… /5 A
Phase current measuring range
0.05 … 10 A~
Sampling frequency
512 samples / cycle
Measurement accuracy
Phase voltage measurement
± 0,1 % (IEC-61557-12 class 0.1) (50 … 500 V~)
Neutral voltage measurement
1% FS
Phase current measurement
± 0,2 % (IEC-61557-12 class 0.2) (0.5 … 10 A~)
Frequency measurement
± 0,1 % (IEC-61557-12 class 0.1)
Active power measurement (kW)
± 0,5 % (IEC-61557-12 class 0.5)
Reactive power measurement (kvar)
± 1 % (IEC 61557-12 class 1)
Active energy measurement (kWh)
± 0,5 % (IEC-62053-22 class 0.5s)
Reactive energy measurement (kvarh)
±1 % (IEC-62053-24 class 1s)
Power factor measurement
± 0,5 % (IEC-61557-12 class 0.5)
Voltage THD
(10 … 100%): Class I (IEC 61000-4-7) Class A (IEC 61000-4-30)
Current THD
(10 … 100%): Class I (IEC 61000-4-7) Class A (IEC 61000-4-30)
Pinst. Flicker
Class F1 (IEC 61000-4-15) Class A (IEC 61000-4-30)
Voltage unbalance (Kd)
± 0,15 % (IEC61000-4-30 class A)
Current unbalance (Kd)
± 0,15 % (IEC61000-4-30 class A)
Wireless communication
Technology / Type
Wi-Fi
Band
2.4 GHz, IEEE 802.11 b / g / n
Radio communication
Technology / Type
4G
Communication Network
Technology / Type
Ethernet 10 Base T - 100 Base Tx self-detectable
Protocol
HTTPS-NTP-SFTP-IEC61850
Connection mechanism
RJ-45
User interface
Resolution of the display
240 x 128 points
LED
6 LED
Keyboard
7 keys
Environmental characteristics
Working temperature
-10…+45 ºC
Storage temperature
-40…+70 ºC
Relative humidity (without condensation)
0 … 95%
Protection class
IP 20 IK 08
Mechanical characteristics
Envelope
Zinc plated sheet steel
Fastening
Rack 19''
Weight (kg)
3,5
Size (mm) width x height x depth
210 x 132.25 x 305.2 (mm)
Standards
Standards
IEC 60529, IEC 61000-4-30, IEC 61000-6-5, IEC 62586-1, IEC 62586-2, IEC 61010-1, IEC 60297-3-100, IEC 62053-22, IEC-62053-23, IEC 17065, IEC 61850, IEEE 1159-3, IEC 61557-12, IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-78
Electrical safety, Installation category
CAT IV (600 V) o CAT III (1000 V) IEC 61010
Electrical safety, Maximum height (m)
2000
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Configuration guide
Service manual
Datasheet
CE-certified

Certificates / Other downloads
CMIM