Power analyzer, three-phase DIN rail

CVM-MINI-HAR-ITF-RS485-C2

CVM-MINI-HAR-ITF-RS485-C2, Power analyzer

Code: M52031.

  • Protocol: Modbus/RTU
  • Insulated input: Yes
  • Communications: RS-485
  • Transistor output: 2
  • Harmonics: U e I (15)
  • Input current: .../5 A | .../1 A
  • Mounting: DIN rail

INFORMATION

Description

Three-phase power analyzer (balanced and unbalanced), assembly on DIN rail, with a very compact size, and 4-quadrant measurement.

Other features include:

  • Current measurement .../5 or .../1 A or .../250 mA, .../333 mV
  • DIN rail format of only 3 modules
  • Assembly on 72 x 72 mm panel with adapter front panel
  • RS-485 Communications (Modbus-RTU) depending on model
  • It features two transistor outputs (programmable)
  • With ITF technology: galvanic insulation protection, depending on the type
  • Selection of parameters to display
  • Selection of the default page
  • Universal power supply (optional)
  • Sealable

Applications

  • Control application on switchboards and low and medium voltage connection points, where an analyzer must be installed on a DIN rail due to space restrictions.
  • Alarm control. Maximum value, minimum value and programmable delay.
  • Control of active or reactive energy using the impulse output.
  • Instantaneous data capture, maximum and minimum values of the electrical parameters measured.

SPECIFICATIONS

AC power supply
Consumption
3 VA
Frequency
50...60 Hz
Nominal voltage
230 Vc.a.(-15…+10%)
Mechanical characteristics
Size (mm) width x height x depth
53 x 85 x 85 (mm)
Envelope
Self-extinguishing V0 plastic
Fastening
DIN rail 46227
Weight (kg)
0,2
Environmental characteristics
Protection class
IP 51 (Front), IP 31 (unmounted)
Relative humidity (without condensation)
5…95%
Working temperature
-10…+50 ºC
Standards
Certifications
CE, UL, VDE
Electrical safety, Maximum height (m)
2000
Electrical safety, Installation category
CAT III 300V / 520V, IEC 61010
Standards
IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 55011
Current measurement circuit
Nominal current (In)
In/5A , In/1 A
Allowable overload
1.2 In
Permanent overload
1.2 In
Maximum input current consumption
0,9 VA
Voltage measurement circuit
Frequency measuring range
45 ... 65 Hz
Voltage measuring range
45 ... 65 Hz
Nominal voltage
300V Ph-N, 520V Ph-Ph
Maximum input voltage consumption
0,7 VA
Communications
Fieldbus
RS-485
Stop bits (ModBus)
1-2
Parity
without, even, odd
Protocol
ModBus RTU
Speed
1200-2400-4800-9600-19200
Peripheral number
0…255
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)
Digital transistor outputs
Pulse width
100 ms
Quantity
2
Type
NPN
Maximum frequency
5 imp / s
Maximum current
50 mA
Maximum voltage
24 Vdc
Measurement accuracy
Phase voltage measurement
0.5% ± 1 digit
Current harmonics (THD)
15
Voltage harmonics (THD)
15

DIMENSIÓN

VÍDEOS

DESCARGAS

User's manual
Technical guide
Dimensions
Configuration guide
Datasheet
Catalogue
CE-certified

ACCESORIOS



TAMBIÉN TE PUEDE INTERESAR