Power analyzer, single-phase DIN rail

SPECIFICATIONS

AC power supply
Nominal voltage
88...276 Vc.a
Frequency
50/60 Hz.
Consumption
2 VA
Voltage measurement circuit
Nominal voltage
110…230 Vac ± 20%
Frequency measuring range
50/60 Hz(MID: 50 Hz)
Current measurement circuit
Nominal current (In)
5 A (min./max.: 0.250…32 A)
Phase current measuring range
0.5…120%
Minimum current measurement
20 mA
Reference current (Iref)
5 A
Transition current
500 mA
Measurement accuracy
Phase voltage measurement
0.5% ± 1 digit
Phase current measurement
0.5% ± 1 digit
Active power measurement (kW)
1% ± 1 digit
Active energy measurement (kWh)
1% ± 1 digit
Power factor measurement
0,5…1
Voltage measurement sensors
Direct measurement (integrated shunt <0.5 mΩ)
Current measurement sensors
Direct measurement (integrated shunt <0.5 mΩ)
Digital transistor outputs
Type
NPN
Maximum voltage
42 Vdc
Maximum current
50 mA
Maximum frequency
1000 imp / kWh
Pulse width
40…200 ms (Programmable)
Environmental characteristics
Working temperature
-5...+55 ºC
Storage temperature
-25… +70 ºC
Relative humidity (without condensation)
5 ... 95%
Protection class
IP 51 (Front), IP 31 (unmounted)
Mechanical characteristics
Envelope
Self-extinguishing UL94-V0 plastic
Weight (kg)
0,082
Size (mm) width x height x depth
18 x 85.5 x 71.6 (mm)
Standards
Standards
EN 50470-1, EN50470-3, EN62053-21, EN62053-23, EN61010-1, EN 61000-6-4, EN 55022 Integrated Energy Meter: Class B EN50470-3 in Active Energy, Class 2 EN62053-23 in Reactive Energy.
Electrical safety, Installation category
CAT III 300V, IEC 61010
Electrical safety, Contamination level/class
Pollution resistance 2
Electrical safety, Maximum height (m)
2000
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

ACCESORIES


TAMBIÉN TE PUEDE INTERESAR