Power analyzer, panel mounted 96x96

CVM-C5-MC-485-I

CVM-C5-MC-485-I

Code: M55895.CONSULTAR DISPONIBILIDAD

  • Power analyzer
  • Protocol: Modbus/RTU
  • Communications: RS-485
  • Transistor output: 0
  • Digital inputs: 1
  • Measuring current Channels: 3
  • Input current: .../250 mA
  • Mounting: Pannel

INFORMATION

Description

The CVM-C5 is a panel mounted (96 x 96 mm) multimeter that records energy values. Compact and intuitive, with 4-quadrant measurement (Consumption and Generation). The CVM-C5 is suitable for Low Voltage installations, in both 3 and 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.

Display features and interface:

  • Quick display of parameters with a single button
  • Clearly displays the electric parameters of the installation
  • Displays the electricity consumption value according to the cost per kWh
  • kgCO2 consumption/generation indicator or according to the energy source
  • Backlit LCD screen
  • Operating hour indicator for preventive maintenance.

Other features:

  • Modbus/RS-485 communications (optional)
  • Measurement with CIRCUTOR’s MC efficient current transformers or .../5 A, .../1 A or .../333 mV transformers.
  • 1 digital output (S0 interface)
  • 1 digital input (tariff or energy source selection)
  • Maximum, minimum values and maximum demand.

Applications

  • Recording and displaying the consumption of energy from two different sources (network/generator set).
  • Generation of an impulse signal associated with the cost, kgCO2 emissions or savings, according to the consumption or generation of energy.
  • Generation of alarms with a transistor output; configurable parameters: Low/High, hysteresis (%), NO/NC, connection/disconnection delay and interlocking.

SPECIFICATIONS

AC power supply
Consumption
3.5 ... 6 VA
Installation category
CAT III 300 V
DC power supply
Nominal voltage
105 ... 272 Vdc ± 10%
Consumption
2 ... 6 W
Installation category
CAT III 300 V
Voltage measurement circuit
Nominal voltage
300V Ph-N, 520V Ph-Ph
Measurement accuracy
Phase voltage measurement
0,50%
Digital inputs
Type
Potential-free contact
Input/output insulation
Optoisolated
Serial communication
Technology / Type
RS-485
Protocol
ModBus RTU
User interface
Visible display area size
60X54 mm
Environmental characteristics
Working temperature
-5…+45 ºC
Protection class
IP 51 (Front), IP 20 (rear)
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Weight (kg)
0,354
Size (mm) width x height x depth
97 x 97 x 97 (mm)
Standards
Standards
IEC 61010, UNE EN 61000-6-2, UNE EN 61000-6-4
Certifications
UL/CSA 61010-1 3rd edition

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

User's manual
Technical guide
Dimensions
Datasheet
Presentation
CE-certified
Product video
Catalogue
Leaflet

ACCESORIES