Power analyzer, panel mounted 96x96

CVM-C5-ITF-485-C

CVM-C5-ITF-485-C, Analyzer

Code: M55834.

  • Mounting: Pannel
  • Modules: 96 x 96

INFORMATION

Description

The CVM-C5 is a panel mounted (96 x 96 mm) multimeter that records energy values. Compact and intuitive, with 4-quadrant measurement (Consumption and Generation). The CVM-C5 is suitable for Low Voltage installations, in both 3 and 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.

Display features and interface:

  • Quick display of parameters with a single button
  • Clearly displays the electric parameters of the installation
  • Displays the electricity consumption value according to the cost per kWh
  • kgCO2 consumption/generation indicator or according to the energy source
  • Backlit LCD screen
  • Operating hour indicator for preventive maintenance.

Other features:

  • Modbus/RS-485 communications (optional)
  • Measurement with CIRCUTOR’s MC efficient current transformers or .../5 A, .../1 A or .../333 mV transformers.
  • 1 digital output (S0 interface)
  • 1 digital input (tariff or energy source selection)
  • Maximum, minimum values and maximum demand.

Applications

  • Recording and displaying the consumption of energy from two different sources (network/generator set).
  • Generation of an impulse signal associated with the cost, kgCO2 emissions or savings, according to the consumption or generation of energy.
  • Generation of alarms with a transistor output; configurable parameters: Low/High, hysteresis (%), NO/NC, connection/disconnection delay and interlocking.

SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
3.5 ... 6 VA
Frequency
49 ... 60 Hz
Nominal voltage
94 ... 240 V ~ ± 10%
DC power supply
Installation category
CAT III 300 V
Consumption
2 ... 6 W
Nominal voltage
105 ... 272 Vdc ± 10%
Environmental characteristics
Protection class
IP 51 (Front), IP 20 (rear)
Relative humidity (without condensation)
5…95%
Storage temperature
-10… +50 ºC
Working temperature
-5…+45 ºC
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Fastening
Panel
Weight (kg)
0,235
Standards
Certifications
UL/CSA 61010-1 3rd edition
Electrical safety, Maximum height (m)
2000
Standards
IEC 61010, UNE EN 61000-6-2, UNE EN 61000-6-4,
Current measurement circuit
Installation category
CAT III 300 V
Nominal current (In)
.../5A , .../1 A
Phase current measuring range
5…110% In
Voltage measurement circuit
Installation category
CAT III 300 V
Frequency measuring range
45 ... 65 Hz
Voltage measuring range
5 ...120% Un
Nominal voltage
300V Ph-N, 520V Ph-Ph
Minimum measurement voltage (Vstart)
10 V Ph-N
Communications
Fieldbus
RS-485
Stop bits (ModBus)
1-2
Parity
without, even, odd
Protocol
ModBus RTU
Speed
1200-2400-4800-9600-19200
User interface
Keyboard
3 keys
Display type
LCD
Visible display area size
60X54 mm
Digital transistor outputs
Pulse width
100 ms
Quantity
1
Type
50 mA
Pulse output, time period (Ton / Toff)
100 ms/100 ms
Maximum frequency
5 imp / s
Maximum current
50 mA
Maximum voltage
24 Vdc
Measurement accuracy
Phase voltage measurement
0,50%

DIMENSIÓN

VÍDEOS

CVM-C5: Multifunction multimeter with energy measurement

DESCARGAS

User's manual
Technical guide
Dimensions
Datasheet
Catalogue
Presentation
CE-certified
Leaflet
Product video

ACCESORIOS