Power analyzer, panel mounted 96 x96

CVM-C11-FLEX+3 MFC-FLEX-125

,

Code: M58563.

    INFORMATION

    Description

    The CVM-C11 is a power analyzer for a panel (96 x 96 mm) with power logging. Ideal for analyzing electrical and consumption quality variables, such as THD% for voltage and current, as well as individual harmonics for each phase up to the 31st. The inclusion of neutral current measurement lets users detect any imbalance, as well as detect overloads in the neutral conductor. Compact and versatile with measurements in 4 quadrants (consumption and generation), suitable for medium- and low-voltage installations.
    Display and interface characteristics:

    • User-defined parameter display.
    • Backlit screen
    • On-screen graphic display of instantaneous active power
    • On-screen graphic display of all quadrants (Q1, Q2, Q3, Q4).
    • On-screen numerical indication of the value of cos φ or PF.
    • On-screen indication of the status of outputs, inputs and/or active tariff.
    • LED alarm indicator
    • Costs, kg of CO2 emitted and operating time per tariff

    Applications

    • Discrimination of power consumption into three tariffs. Ideal for determining consumption during three different work shifts or from three different energy sources (grid, generator and photovoltaic generation), using the digital inputs.
    • Generation of an impulse signal related to cost, kg of CO2 emitted or proportional to energy consumption or generation.
    • Alarm control (2 relay outputs + 2 digital outputs) for any instantaneous parameter, whether measured or calculated. Adjustable based on maximum/minimum value, hysteresis (%), NO/NC, connection/disconnection delay and interlocks.

    SPECIFICATIONS

    AC power supply
    Nominal voltage
    100 ... 270 V ~ ± 10%
    Frequency
    50 ... 60 Hz
    Consumption
    2,5 ... 5,5 VA
    Installation category
    CAT III 300 V
    DC power supply
    Nominal voltage
    100 ... 270 Vdc ± 10%
    Installation category
    CAT III 300 V
    Voltage measurement circuit
    Nominal voltage
    230V Ph-N, 380V Ph-Ph
    Frequency measuring range
    45 ... 65 Hz
    Input impedance
    > 1.7 MΩ
    Minimum measurement voltage (Vstart)
    10 V ~
    Maximum value
    300 VF-N /520 VF-F
    Installation category
    CAT III 300 V
    Current measurement circuit
    Nominal current (In)
    100 mV/kA (without/sin sensors MFC-FLEX)
    Minimum current measurement
    0.2 mV
    Installation category
    CAT III 300 V
    Measurement accuracy
    Phase voltage measurement
    0.2% (5 ...120% Un)
    Phase current measurement
    0.5% (10 ... 300% In), without/sin MFC-FLEX
    Active power measurement (kW)
    1% without/sin MFC-FLEX
    Reactive power measurement (kvar)
    2% without/sin MFC-FLEX
    Digital transistor outputs
    Quantity
    2
    Type
    NPN
    Maximum voltage
    24 Vdc
    Maximum current
    50 mA
    Maximum frequency
    16 imp / s
    Pulse width
    30 ms a 400 ms (Programmable)
    Digital relay outputs
    Electrical life (at maximum load)
    60x103 cycles
    Mechanical life
    10x106 cycles
    Maximum switching capacity
    625 VA / 75 W (AC1)
    Digital inputs
    Quantity
    2
    Type
    NPN
    Input/output insulation
    2000 V
    Serial communication
    Technology / Type
    RS-485
    Protocol
    ModBus RTU|BACnet
    User interface
    Display type
    LCD Custom COG
    Keyboard
    3 keys
    Environmental characteristics
    Working temperature
    -25 …+70 ºC
    Storage temperature
    -25 …+75 ºC
    Relative humidity (without condensation)
    5 ... 95%
    Protection class
    IP 54 (Front), IK 08
    Mechanical characteristics
    Envelope
    Self-extinguishing V0 plastic
    Fastening
    Panel
    Size (mm) width x height x depth
    96 x 96 x 67.2 (mm)

    DIMENSIONS

    CONNECTIONS

    VIDEOS

    DOWNLOADS

    User's manual
    Technical guide
    3D
    Dimensions
    Diagram connection
    Datasheet
    CE-certified
    Other Certificates
    Catalogue
    Leaflet

    ACCESORIES