Power analyzer, colour display, panel mounted

CVM-B150-ITF-485-ICT2

CVM-B150-ITF-485-ICT2, Power analyzer

Code: M56111.

  • Protocol: Modbus/RTU | BACnet
  • Energy accuracy: 0,5 S (.../5A)
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Input current: .../5 A | .../1 A | .../250 mA
  • Mounting: Pannel
  • Modules: 144 x 144

INFORMATION

Description

The CVM-B100 and CVM-B150 units are panel mounted three-phase power analyzers (dimensions: 96x96 and 144x144 mm, respectively). Both offer 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.

The CVM-B100 and CVM-B150 high-performance units feature a measurement engine that allows the user to analyse many different electrical parameters, in addition to offering a large variety of optional expansion modules for the same unit.

Features:

  • Format: 96x96 (CVM B100) and 144x144 (CVM B150)
  • High-resolution VGA colour screen
  • IP 65 front panel protection (with sealing joint)
  • 5 voltage inputs (3 phases + neutral + earth) 1000 Vf-f
  • 4 Current inputs, ITF
  • Class 0.2 voltage and current accuracy
  • Class 0.5S energy accuracy
  • Expandable unit, up to 4 modules, combining digital and analogue outputs, Modbus/TCP, MBus, LonWorks, Profibus, XML/Web
  • Modular (optional addition of expansion modules)
  • Touch-sensitive movement buttons
  • Universal power supply source
  • RS485 communications port (Modbus/RTU and BACnet protocols)
  • Customisation of parameters to be displayed
  • Operating hour indicator for preventive maintenance.

Other features:

  • Innovative SCV interface (Slide, Choose & View) for versatile data display, enabling the customisation of the parameters displayed on the screen
  • Electrical parameters: instantaneous, maximum, minimum (with date and time) and demand
  • Incremental electrical parameters (energy), times, costs, emissions
  • 3 Tariffs (can be selected via the digital input or RS485 communications)
  • Capable of showing costs and kgCO2 emission sources on the screen, depending on the energy consumed or generated
  • 2 Relay outputs for alarms with delay, times, ON and OFF, etc.
  • 2 transistor outputs for alarms or impulse generation, with all the possible configuration parameters
  • 2 digital inputs, with control over the selection of the unit’s tariffs or configurable for monitoring purposes, with RS-485 Modbus communications, monitoring of logical states of other electromechanical units. (RCCBs, thermal-magnetic circuit breakers, etc.)

Applications

  • Control and monitoring of all electrical parameters measured in any electric distribution panel and low and high-voltage connection points.
  • 4 alarms (2 per transistor and 2 per relay), fully and independently programmable: low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
  • Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours)
  • Transducer that converts analogue signals to any instantaneous parameter that the unit can measure or calculate, with built-in expansion modules with analogue outputs.
  • Display of process signals, with a built-in expansion module with analogue inputs; optional reporting of these signals to SCADA systems through communication systems
  • Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
  • Autonomous datalogger with web server, connected to a M-CVMAB-Datalogger module. Enables direct monitoring of the historical data stored in the unit via a conventional web browser.

400 Hz Applications

CVM-B150 provides a version adapted to 400 Hz networks specially designed for applications such as:

  • Aeronautical
  • Astronautics
  • Naval
  • Military

SPECIFICATIONS

AC power supply
Nominal voltage
100 ... 240 V ~
Frequency
45 ... 65Hz
Consumption
máx. 29.4 VA
Installation category
CAT III 300 V
DC power supply
Nominal voltage
120 … 300 Vdc
Consumption
max. 11.9 W
Installation category
CAT III 300 V
Voltage measurement circuit
Voltage measuring range
20…600 V~
Frequency measuring range
40…70Hz
Input impedance
1.2MΩ
Minimum measurement voltage (Vstart)
10 V~
Installation category
CAT III 600V
Maximum input voltage consumption
0,15VA
Current measurement circuit
Nominal current (In)
…/5A, …/1A, …/0.250A
Phase current measuring range
0.01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A)
Neutral current measuring range
0.02...0.5A (.../0.250A, calculated)
Maximum pulse current
100 A
Minimum current measurement
0,01 A (…/5A, …/1A, …/0,250A
Maximum input current consumption
0,9 VA
Installation category
CAT III 600 V
Measurement accuracy
Phase voltage measurement
Class 0.2 ±1 digit (20…600 Vca, …/5A, …/1A, …/0.250A)
Neutral voltage measurement
Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
Phase current measurement
class 0,2 ±1 digit 0.05…8A (…/5A),0.01…1.2A ( …/1A), 0,01 … 0,3A (…/0,250A)
Neutral current measurement
class 1 ±1 digit 0.05…6A (…/5A),0.05…1.2A ( …/1A), calculated (…/0.250A)
Frequency measurement
Class 0.1 (…/5A, …/1A, …/0.250A)
Active power measurement (kW)
(Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Apparent power measurement (kVA)
(Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Reactive power measurement (kvar)
(Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
Active energy measurement (kWh)
(IEC 62053-22) Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
Reactive energy measurement (kvarh)
(IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
Power factor measurement
class 0,5 (…/5A, …/1A, …/0.250A)
Voltage THD
class 1 (…/5A, …/1A, …/0.250A)
Voltage harmonics (THD)
class 1 (…/5A, …/1A, …/0.250A)
Current THD
class 1 (…/5A, …/1A, …/0.250A)
Current harmonics (THD)
class 1 (…/5A, …/1A, …/0.250A)
Digital transistor outputs
Quantity
2
Type
NPN
Maximum voltage
48 Vdc
Maximum current
130 mA
Maximum frequency
1 kHz
Pulse width
1 ms
Pulse output, time period (Ton / Toff)
0,3 ms/0,7 ms
Digital relay outputs
Electrical life (at maximum load)
3x104 cycles
Mechanical life
1x107 cycles
Maximum switching capacity
1500 VA
Digital inputs
Quantity
2
Type
Potential-free contact
Input/output insulation
4 kV
Maximum short-circuit current
5 mA
Maximum open circuit voltage
15 Vdc
Serial communication
Technology / Type
RS-485 / BACnet
Protocol
ModBus/RTU, BACnet
User interface
Display type
TFT color
Resolution of the display
VGA (640x480)
Display format
4:3
Visible display area size
5.6"
LED
3 LED (CPU-Keys-ALARM)
Keyboard
Capacitive, 3 keys
Environmental characteristics
Working temperature
-10…+60 ºC
Storage temperature
-20… +80 ºC
Relative humidity (without condensation)
5 ... 95%
Protection class
IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted)
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Fastening
Panel 138x138
Weight (kg)
0,704
Size (mm) width x height x depth
144 x 144 x 96 (mm)
Standards
Standards
IEC 61010-1 (1rd. Edition), UNE-EN 61000-6-2, UNE-EN 61000-6-4, IEC 60664-1, IEC 61010-2-030 (First Edition). Measurement according to IEC 61557-12
Certifications
UL 61010-1 3rd edition, CAN/CSA-C22.2 No.61010-1 3rd. edition 2012-05
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

(1/4) Programming CVM-B100 / CVM-B150: Basic analyzer programming
(2/4) Programming CVM-B100 / CVM-B150: Programming transformation ratios
(3/4) Programming CVM-B100 / CVM-B150: Parameter Settings
(4/4) Programming CVM-B100 / CVM-B150: Digital inputs and outputs

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Datasheet
Presentation
CE-certified
Product video
Video Installation
Other Certificates
Software & Firmware
Catalogue
Leaflet

ACCESORIES