Power analyzer, panel mounted 96 x96

CVM-C10-ITF-485-ICT2

CVM-C10-ITF-485-ICT2, Power analyzer

Code: M55911.

  • Protocol: Modbus/RTU | BACnet
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Measuring current Channels: 3
  • Harmonics: 31
  • Input current: .../5 A | .../1 A
  • Mounting: Pannel
  • Modules: 96 x 96

INFORMATION

Description

The CVM-C10 is a panel mounted (96 x 96 mm) power analyzer that records energy values. Compact and versatile, with 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits,
two-phase circuits with or without neutral, single-phase circuits or ARON connections.

Display features and interface:

  • Backlit touch-screen (capacitive)
  • Analogue display of instantaneous parameters (power, maximum power reached and cos φ or PF)
  • Backlit display
  • Alarm LED indicator.
  • Tariff cost
  • Operating hour indicator for preventive maintenance

Applications

  • Record the energy consumption from three different sources: network, generator set or photovoltaic energy generation system.
  • Generation of an impulse signal associated with the cost, kgCO2 emissions or savings, according to the consumption or generation of energy.
  • Selection of tariffs with digital inputs. Perfect to calculate costs in three different work shifts.
  • Programs alarms on any instantaneous parameter measured or calculated. Configurable parameters: Low/High, hysteresis (%), NO/NC,
    connection/disconnection delay and interlocking.

SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
4 ... 6 VA
Frequency
50 ... 60 Hz
Nominal voltage
95 ... 240 V ~ ± 10%
DC power supply
Installation category
CAT III 300 V
Consumption
2 ... 6 W
Nominal voltage
105 ... 272 Vdc ± 10%
Mechanical characteristics
Size (mm) width x height x depth
96 x 96 x 60.9 (mm)
Envelope
Self-extinguishing V0 plastic
Fastening
Panel
Weight (kg)
0,314
Environmental characteristics
Protection class
IP 51 (Front), IP 64 (with accessory), IP 21 (rear)
Relative humidity (without condensation)
5 ... 95%
Storage temperature
-10… +65 ºC
Working temperature
-10 …+60 ºC
Standards
Certifications
UL/CSA 61010-1 3rd edition, UL, VDE
Electrical safety, Maximum height (m)
2000
Standards
UNE EN 61010, UNE EN 61000-6-3, UNE EN 61000-6-1, IEC 664, VDE 0110, UL 94, BS EN 61000-6-2, BS EN 61000-6-4
Current measurement circuit
Installation category
CAT III 300 V
Nominal current (In)
.../5A , .../1 A
Phase current measuring range
2 ... 120% In
Maximum input current consumption
0,9VA
Maximum pulse current
100 A
Minimum current measurement
10 mA
Voltage measurement circuit
Installation category
CAT III 300 V
Frequency measuring range
45 ... 65 Hz
Voltage measuring range
5 ...120% Un
Nominal voltage
300V Ph-N, 520V Ph-Ph
Minimum measurement voltage (Vstart)
15 V
Communications
Fieldbus (BACnet)
MS/TP
Fieldbus (ModBus)
RS-485 / RTU
Stop bits (BACnet)
1
Stop bits (ModBus)
1-2
Parity (BACnet)
non
Parity
without, even, odd
Protocol
ModBus/BACnet
Speed
9600-19200
User interface
LED
3 LED
Keyboard
3 keys
Display type
LCD Custom COG
Digital inputs
Input/output insulation
Optoisolated
Quantity
2
Type
NPN Potential-free contact
Digital relay outputs
Electrical life (at maximum load)
60x103 cycles
Mechanical life
10x106 cycles
Maximum switching capacity
1500 VA
Digital transistor outputs
Pulse width
30 ms a 500 ms (Programmable)
Quantity
2
Type
NPN salida
Maximum frequency
16 imp / s
Maximum current
50 mA
Maximum voltage
24 Vdc
Measurement accuracy
Phase voltage measurement
0.5% ± 1 digit

DIMENSIONS

CONNECTIONS

VIDEOS

CVM-C10. Electrical power analyzer with energy measurement

Programming CVM-C10: Basic analyzer programming
Programming CVM-C10: Configuration of communications
Programming CVM-C10: Activate harmonics display
Programming CVM-C10: Alarm monitoring
Programming CVM-C10: Emissions, costs and consumption
Programming CVM-C10: Digital output to relay/transistor

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Configuration guide
Datasheet
Catalogue
Presentation
CE-certified
Leaflet
Product video
Video Installation
Other Certificates
Software & Firmware

ACCESORIES