Power analyser 96 x 96 panel with flexible clamps

CVM-C10-FLEX-IN-485-I2

CVM-C10-FLEX-IN-485-I2, Power analyzer panel 96 x 96 compatible with flexible clamps

Code: M55963.

  • Protocol: Modbus/RTU | BACnet
  • Communications: RS-485
  • Digital inputs: 2
  • Measuring current Channels: 4
  • Harmonics: 31
  • Input current: Rogowski
  • Mounting: Pannel
  • Modules: 96 x 96

INFORMATION

Description

Compact and versatile power analyser, with 4-quadrant measurement (Consumption and Generation), suitable for High, Medium and Low-Voltage installations, since it can process high voltage:current transformation ratios of up to 2000 A. Measures current with flexible Rogowski sensors.

Capable of adapting to any type of electrical network topology, from single-phase lines, two-phase lines with or without neutral to three-phase lines with or without Neutral. The CVM-C10-Flex calculates the sensitivity of the measurement range scale automatically, according to the nominal value of the detected current, up to a full-scale of 2000 A. (Twice the full-scale value of measured current, 1000 A).

The flexible sensors feature a magnetic lock, which allows the sensors to be sealed. They are robust and can withstand frequent assembly and disassembly procedures, thanks to these magnetic lock.

Quick installation on distribution panels or switchboards of the unit, thanks to its flexible current sensors. Self-adjustment of the scale sensitivity. Does not require the current primary to be programmed. (1000 A by default, factory setting). Remote correction of errors associated with the incorrect connection of the unit to the electrical installation via remote communication systems (PowerStudio).

Display features and interface:

  • Backlit keypad (capacitive)
  • Analogue display for instantaneous parameters (power, maximum power reached and cos φ or PF)
  • Backlit display
  • Cost by tariff

Operating time indicator for preventive maintenance.

  • The unit has the following functions:
  • Recording of the energy consumption from three different sources: network, generator set or photovoltaic energy generation system.
  • Selection of tariffs with digital inputs. Perfect for calculating costs in three different work shifts.

Applications

  • Management Systems that require roaming measuring points.
  • Distribution panels or switchboards that cannot stop the installation of a measuring unit.

SPECIFICATIONS

AC power supply
Nominal voltage
95 ... 240 V ~ ± 10%
Frequency
50 ... 60 Hz
Consumption
4 ... 6 VA
Installation category
CAT III 300 V
DC power supply
Nominal voltage
105 ... 272 Vdc ± 10%
Consumption
2 ... 6 W
Installation category
CAT III 300 V
Voltage measurement circuit
Nominal voltage
300V Ph-N, 520V Ph-Ph
Voltage measuring range
5 ...120% Un
Frequency measuring range
45 ... 65 Hz
Minimum measurement voltage (Vstart)
15 V
Installation category
CAT III 300 V
Current measurement circuit
Nominal current (In)
…/100 mV c.a
Neutral current measurement
…/100 mV~
Phase current measuring range
0.2 … 200% In
Maximum pulse current
2 In
Minimum current measurement
0,2 mV~
Maximum input current consumption
0,004 VA
Installation category
CAT III 300 V
Measurement accuracy
Phase voltage measurement
0.5% ± 1 digit (Without sensors), ± 0.5% + 1 decimal (With sensors)
Digital inputs
Quantity
4
Type
NPN Potential-free contact
Input/output insulation
Optoisolated
Serial communication
Technology / Type
RS-485 / BACnet
Protocol
ModBus/RTU, BACnet
User interface
Display type
LCD Custom COG
LED
3 LED
Keyboard
3 keys
Environmental characteristics
Working temperature
-5 … +45 ºC
Storage temperature
-10… +50 ºC
Relative humidity (without condensation)
5 ... 95%
Protection class
IP 51 (Front), IP 64 (with accessory), IP 21 (rear)
Mechanical characteristics
Envelope
Self-extinguishing V0 plastic
Fastening
Panel
Weight (kg)
0,268
Size (mm) width x height x depth
96 x 96 x 60.9 (mm)
Standards
Standards
UNE EN 61010, UNE EN 61000-6-3, UNE EN 61000-6-1, IEC 664, VDE 0110, UL 94, BS EN 61000-6-2, BS EN 61000-6-4
Certifications
UL, VDE
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

Programming CVM-C10: Basic analyzer programming
Programming CVM-C10: Configuration of communications
Programming CVM-C10: Activate harmonics display
Programming CVM-C10: Alarm monitoring
Programming CVM-C10: Emissions, costs and consumption
Programming CVM-C10: Digital output to relay/transistor

DOWNLOADS

User's manual
Technical guide
3D
Dimensions
Diagram connection
Configuration guide
Datasheet
Presentation
CE-certified
Product video
Video Installation
Software & Firmware
Catalogue
Leaflet

ACCESORIES






TAMBIÉN TE PUEDE INTERESAR