Narrow section transducers

CVE-A

CVE-A, Transducer Vac.

Code: M25011.

  • Output type: 2
  • Analog output: 4…20mA
  • Measure: 300 Vac
  • Paramètre: V ~

INFORMATION

Description

The CVE-A and CVE-AP transducers, convert A.C voltage to D.C process indicator signal.

The analog output is directly proportional to the input signal, calibrated as a RMS with sinus signal of 50Hz.

SPECIFICATIONS

AC power supply
Nominal voltage
115/230 Vca (-10…+10 %)
Frequency
40…90 Hz
Consumption
2,5 VA
DC power supply
Nominal voltage
9-18 / 18-36 Vdc 36-72 / 90-140 Vdc
Consumption
2,5 VA
Voltage measurement circuit
Nominal voltage
0…660 V
Voltage measuring range
5…120 % Vn
Frequency measuring range
45/65 Hz
Maximum permanent measurement voltage
1000 V
Consumption
0,2 VA
Measurement accuracy
Phase current measurement
0,5 % FS
Analogue outputs
Displaced output
0,2…2 V / 2…10 V / 4…20 mA
Current mode, nominal range
0…10, 20 mAac
Voltage mode: nominal output range
0…5, 10 Vac
Analogue inputs
Load impedance in voltage
> 500 Ω
Load impedance in current
< 500 Ω
Response time
< 300 ms (0…99 % Vn)
Ripple (effective RMS value)
< 2 %
Environmental characteristics
Working temperature
-10…+60 °C
Storage temperature
-40….+70 °C
Protection class
IP 20 (Terminals) IP 40 (case)
Standards
Standards
IEC 529, IEC 688, IEC 801, EN 50081-1, EN 50082-1, IEC 1010
Electrical safety, Maximum height (m)
2000
Mechanical characteristics
Weight (kg)
0,06
Size (mm) width x height x depth
20 x 70 x 110 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Dimensions
Diagram connection
Datasheet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR