Current transformers with converter 4...20 mA or 0…20 mA

TC6 020 50A

TC6 020 50A, Current transformers narrow section

Code: M72031.

  • Flat strip(mm): 40 x 10
  • Inner diameter (mm): 28
  • Analog output: 0...20 mA
  • Measurement Range (A): 50
  • Input current: 50 A
  • Transformer type: Current transformer with 4 ... 20 mA converter

INFORMATION

Description

  • Self-powered: does not need an auxiliary power supply.
  • Primary current: from 50 to 300 Aac, depending on the type
  • Secondary current: 0 ... 20 mA
  • Internal diameter: from 28 to 44 mm, depending on the type
  • Busbar dimensions: from 40 x 10 mm to 60 x 12 mm

Applications

Used in power lines to obtain a current proportional to the primary current rated at 0..20 mA / 4...20 mA in the secondary

SPECIFICATIONS

Electrical characteristics
Safety factor (SF)
FS < 5
Mechanical characteristics
Size (mm) width x height x depth
64 x 80.5 x 44 (mm)
Envelope
Plastic wrap V0 self-extinguishing
Weight (kg)
0,349
Environmental characteristics
Thermal Class
Class B (+130 ºC)
Specific technical characteristics of current sensors
Inner diameter Ø (mm)
28
Operating voltage
0,72 kV~ max.
Current measurement circuit
Nominal frequency
50 / 60 Hz
Primary current measurement
200 A
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Transformation ratio
0 … 20 mA