Measuring transformers encapsulated in resin

TRM140 1500/5A

TRM140 1500/5A, Measuring transformers encapsulated in resin

Code: P50153.

  • Inner diameter (mm): 140
  • System: Single-phase
  • Class 0,5 Power (VA): 25
  • Measurement Range (A): 1500/5
  • Input current: 1500 A
  • Transformer type: Encapsulated in resin

INFORMATION

Description

Resin-coated current transformer, busbar. Other characteristics:

  • From 75 to 5000 A
  • Inner diameter from 30 to 180 mm, according to type 
  • Secondary .../5 A ( .../1 A on request)

Applications

These transformers have been conceived to convert nominal currents in any installation to current values adjusted to measurement devices. Its synthetic resin increases its resistance to adverse environmental conditions.

SPECIFICATIONS

Electrical characteristics
Power
25 VA (Class 0,5)
Insulation voltage between terminals S1-S2
3 kV
Mechanical characteristics
Size (mm) width x height x depth
223 x 269 x 40 (mm)
Envelope
Self-extinguishing V0, synthetic resin
Weight (kg)
2,2
Environmental characteristics
Thermal Class
Class B (+130 ºC)
Specific technical characteristics of current sensors
Inner diameter Ø (mm)
140
Operating voltage
0,72 kV~ max.
Current measurement circuit
Nominal frequency
50 / 60 Hz
Primary current measurement
1500 A
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Transformation ratio
… / 5 A
Standards
Standards
IEC 60044-1 / UNE EN 60044-1

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

3D
Dimensions
Datasheet
CE-certified

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR