Current transformers, split core

STQ-24 300/5A

STQ-24 300/5A, Split core current transformer

Code: M7371A.

  • System: Single-phase
  • Class 1 Power (VA): 1
  • Measurement Range (A): 300/5
  • Input current: 300 A
  • Transformer type: Split core

INFORMATION

Description

Open-core current transformers with compact dimensions for easy installation. This type of transformer is very easy to install and uninstall on compact panels where the reduced space makes it difficult to take current measurements. In addition, their open-core design means that they can take measurements without having to interrupt the electric supply. The primary current measurement range is from 100 A to 300 A using different secondary outputs (.../1A, .../5A or .../250mA) with a maximum admissible cable diameter of 24 mm.

Applications

Quick and easy assembly are a fundamental aspect when taking temporary measurements in an electrical installation. STQ-24 transformers can take energy measurements together with CIRCUTOR's power analyzers or energy meters (CVM-MINI, CVM-NET, CVM-C, CVM-B, EDMk, etc.) without having to interrupt the electric supply. The open-core design of the transformer makes it very easy to install and allows installers to take electrical measurements in less time.

SPECIFICATIONS

Electrical characteristics
Insulation voltage between terminals S1-S2
3 kV
Safety factor (SF)
5
Power
1 VA (class 1)
Current measurement circuit
Primary current measurement
300 A
Allowable overload
1,2 In
Transformation ratio
… / 5 A
Nominal frequency
50 / 60 Hz
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Specific technical characteristics of current sensors
Operating voltage
0,72 kV~ máx.
Inner diameter Ø (mm)
24
Measurement accuracy
Accuracy
Clase 1/3
Environmental characteristics
Working temperature
-20 … +75 ºC
Storage temperature
-20 … 75 ºC
Thermal Class
Class B (+130 ºC)
Relative humidity (without condensation)
15 … 85%
Protection class
IP 20
Mechanical characteristics
Envelope
PC LexanTM 940-701
Weight (kg)
0,2
Size (mm) width x height x depth
53 x 70 x 43.2 (mm)
Standards
Standards
UNE-EN 61869-1, UNE-EN 61869-2
Electrical safety, Maximum height (m)
1000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Technical guide
Diagram connection
Datasheet