Current transformers, split core

TP-23 300/5A

TP-23 300/5A

Code: M70115.CONSULTAR DISPONIBILIDAD

  • Transformer
  • Flat strip(mm): 20 x 30
  • Class 0,5 Power (VA): 1,5
  • Class 1 Power (VA): 4
  • Class 3 Power (VA): 6
  • Measurement Range (A): 300/5
  • Input current: 300/5 A

INFORMATION

Description

Open-core transformers that can measure current without having to interrupt the electric supply. In other words, the installation does not have to be dismantled in order to install them.

  • Range: 100 to 5000 A
  • Busbar dimensions: 20 x 30 mm to 80 x 160 mm
  • The transformer certificate is attached.

Applications

Converting a high nominal current to a lower current so that it can be measured by the unit. They have a split core and can be installed with no need to interrupt the installation's power supply.

SPECIFICATIONS

Electrical characteristics
Safety factor (SF)
FS 10
Power
4 VA (Class 1)
Current measurement circuit
Primary current measurement
300 A
Transformation ratio
… / 5 A
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Specific technical characteristics of current sensors
Operating voltage
0,72 kV~ max.
Environmental characteristics
Working temperature
-5 ... 40 ºC
Thermal Class
Class B (+130 ºC)
Standards
Standards
IEC 44-1, UNE 21 088-1, UL 94, VDE 0414
Mechanical characteristics
Weight (kg)
0,7
Size (mm) width x height x depth
110 x 89 x 58 (mm)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Datasheet
CE-certified

ACCESORIES