R45 flexible clamps

KIT 3 -FLEX-R45

KIT 3 -FLEX-R45, Flexible clamp

Code: M81631.

  • Lenght: 45 cm
  • Nr Sensors: 3
  • Usefull diam.(mm): 140
  • Measurement Range (A): 10 … 100 A / 100 … 1000 A / 1000 … 10000 A
  • IΔn min.(A): 1
  • I min: 1 | 10 | 500

INFORMATION

Description

The flexible current sensor can take alternating current measurements from any installation with a full rejection of DC components, a very low consumption of power, with no saturation problems, a low temperature dependence and a very good linearity. The flexible sensor has been designed according to the Rogowsky coil principle, measuring alternating current irrespective of the position of the conductor. The current conductor must not be near the coil cable joint, since the degree of error increases in this area. Its centred location also reduces the impact of external magnetic fields. Thanks to the flexibility of the current sensor, one or more conductors can be surrounded, regardless of their shape, to perform current measurement actions.

Applications

These flexible current sensors have been specially designed for the MYeBOX-150 and MYeBOX-1500 portable power analysers.

SPECIFICATIONS

Current measurement circuit
Nominal frequency
50Hz/60 Hz.
Specific technical characteristics of current sensors
Linearity
(10…100%) ± 0,2 %
Accuracy
± 1 %
Output voltage
76 µV/A a 50 Hz
Maximum temperature coefficient
± 0,05 %
Position sensitivity (cable connection)
± 3 %
External fields
± 2 %
Environmental characteristics
Working temperature
-20...85 °C
Storage temperature
-40…85 °C
Relative humidity (without condensation)
15…85 %
Protection class
IP 20 / IP 54 with terminal cover (optional) (for models Ø 85, 100, 116 mm)
Mechanical characteristics
Envelope
sensor material: Self-extinguishing UNE 21031 90 °C / Material couplings: PA V-0
Weight (kg)
0,7
Standards
Standards
Dielectric strength IEC 61010-2-32 ( 5,4 kV 50 Hz)
Electrical safety, Installation category
1000V CAT III / 600V CAT IV
Electrical safety, Contamination level/class
Pollution resistance 2
Electrical safety
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Technical guide
Datasheet

ACCESORIES

TAMBIÉN TE PUEDE INTERESAR