Automatic capacitor bank with reactive relay.

,

Code:

    SPECIFICATIONS

    AC power supply
    Frequency
    50 Hz
    Electrical characteristics
    Losses (W)
    < 0,5 W/kvar
    Discharge resistance
    75 V / 3 min
    Surge
    10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
    Manoeuvre voltage
    Contactors: 230 V
    Reinforcement voltage
    440 V
    Tolerance C
    -5% / 10 %
    Voltage
    400 V (other voltages on request)
    Mechanical characteristics
    Size (mm) width x height x depth
    215 x 500 x 166 (mm)
    Envelope
    Thermoplastic. RAL 7035
    Fastening
    Vertical
    Ventilation
    Natural or forced according to options
    Weight (kg)
    3,5
    Environmental characteristics
    Protection class
    Marked on the label
    Relative humidity (without condensation)
    80%
    Working temperature
    Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 55 ºC, minimum: -50 ºC
    Current measurement circuit
    Permanent overload
    1,3 In
    Transformation ratio
    In/5 A
    Standards
    Electrical safety, Maximum height (m)
    1000 máx. (para altitud mayor prever siempre ventilación forzada)
    Standards
    IEC 60831-1, IEC 61921, IEC 60439
    Features / performance
    Optional
    Other frequencies, consult.

    DIMENSIONS

    CONNECTIONS

    VIDEOS

    DOWNLOADS

    ACCESORIES


    TAMBIÉN TE PUEDE INTERESAR