SPECIFICATIONS

AC power supply
Frequency
50 Hz
Electrical characteristics
Voltage
400 V (other voltages on request)
Reinforcement voltage
440 V
Surge
10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Manoeuvre voltage
Contactors: 230 V
Discharge resistance
75 V / 3 min
Tolerance C
-5% / 10 %
Losses (W)
< 0,5 W/kvar
Current measurement circuit
Permanent overload
1,3 In
Transformation ratio
In/0,25 A
Environmental characteristics
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 55 ºC, minimum: -50 ºC
Relative humidity (without condensation)
80%
Protection class
IP 21
Mechanical characteristics
Envelope
Thermoplastic. RAL 7035
Fastening
Vertical
Ventilation
Natural or forced according to options
Weight (kg)
7
Size (mm) width x height x depth
270 x 500 x 166 (mm)
Features / performance
Optional
Other frequencies, consult.
Standards
Standards
IEC 60831-1, IEC 61921, IEC 60439
Electrical safety, Maximum height (m)
1000 máx. (para altitud mayor prever siempre ventilación forzada)