Double voltimeters

2EC144 2x.../110V

2EC144 2x.../110V, Voltmeter

Code: M13842.

  • Scale: 90º
  • Accuracy: 1,5
  • Measurement Range (V): 2x.../110
  • Device: 2EC144
  • Modules: 144x144

INFORMATION

Description

  • Does not need an auxiliary power supply
  • DIN box with dimensions 96 and 144 mm
  • Class 1.5
  • Double scale

Applications

For the measurement and comparison of alternating currents from two generators or a generator in the network, when connected in parallel.

SPECIFICATIONS

Electrical characteristics
Insulation voltage, circuit
2kV a 50 Hz < 1min entre mecanismo y caja
Voltage measurement circuit
Nominal voltage
230 V ~
Maximum permanent measurement voltage
1,2 Vn permanent rated voltage / 2 Vn during 5s
Consumption
1 … 4 VA
Sampling frequency
20 … 100 Hz
Measurement accuracy
Accuracy
1,5 % FE
Environmental characteristics
Working temperature
+10 … +30 °C
Storage temperature
-25 … +40 °C
Protection class
Panel: IP 52 (Front), IP 00 (Terminals)
Mechanical characteristics
Fastening
Panel
Weight (kg)
0,43
Size (mm) width x height x depth
144 x 144 x 71.8 (mm)
Standards
Standards
BS 89, UNE-EN 60051, IEC 144, UL94, DIN 43780, IEC 51, UNE 21318
Certifications
UL

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Datasheet

ACCESORIES