Induction phasemeters

PIC144B 400 V

PIC144B 400 V, Phasemeter

Code: M13646.CONSULTAR DISPONIBILIDAD

  • Scale: 360º, P1
  • System: Balanced three-phase
  • Accuracy: 1,5
  • Measurement Range (V): 400
  • Modules: 144x144

INFORMATION

Description

  • Does not need an auxiliary power supply
  • DIN box with dimensions 96 and 144.
  • Class 1.5
  • Balanced and unbalanced single and three-phase circuits.
  • 4 quadrants

Applications

Measurement of cosφ in balanced or unbalanced single and three-phase circuits.

SPECIFICATIONS

Electrical characteristics
Insulation voltage, circuit
2 kV a 50 Hz <1 min entre mecanismo y caja
Voltage measurement circuit
Consumption
20 mA
Sampling frequency
49,5 … 50,5 Hz / 59,4 … 60,6 Hz
Current measurement circuit
Nominal current (In)
… 5 A
Allowable overload
1,2 In permanent / 5 In during 30s / 10 In during 5s / 40 In during 1s
Consumption
4 VA
Sampling frequency
20 … 100 Hz
Measurement accuracy
Accuracy
± 1,5 % FE
Environmental characteristics
Working temperature
+10 … +30 °C
Storage temperature
-25…+40 °C
Protection class
Panel: IP 52 (Front), IP 00 (Terminals)
Mechanical characteristics
Fastening
Panel
Weight (kg)
1,46
Size (mm) width x height x depth
144 x 144 x 102 (mm)
Standards
Standards
BS 89, UNE-EN 60051, IEC 144, UL 94, DIN 43780, IEC 51, UNE 21318
Certifications
CE, UL
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Diagram connection
Datasheet

ACCESORIES