Maximeter ammeters

EMC72 .../5A

EMC72 .../5A, Maximeter

Code: M12622.

  • Scale: Doble escala 90º, P1,2, hierro móvil P2
  • Accuracy: Bimetálico: 3 Hierro móvil:1,5
  • Measurement Range (A): …/5 A
  • Modules: 72x72

INFORMATION

Description

  • Does not need an auxiliary power supply
  • DIN boxes with dimensions 48, 72, 96 and 144
  • Class 3
  • Measurement in AC of .../5 A (on demand.../ 1 A)
  • Exchangeable scales for MC48, MC72, MC96, MM 45, EMC72, EMC96
  • Thermal inertia times of 15 min (on demand, 8 and 30 min)

Applications

To control the alternating current and measure long overloads in the same unit, integrated within a determined period.

SPECIFICATIONS

Electrical characteristics
Insulation voltage, circuit
2kV a 50 Hz < 1min entre mecanismo y caja
Current measurement circuit
Allowable overload
1,5 In permanent / 15 In during 1s
Consumption
4,25 VA
Measurement accuracy
Accuracy
±3 % Bim. / ±1,5 % HM
Environmental characteristics
Working temperature
+10 … +30 °C
Storage temperature
-25…+40 °C
Protection class
Panel: IP 52 (Front), IP 00 (Terminals)
Mechanical characteristics
Fastening
Panel
Weight (kg)
0,125
Size (mm) width x height x depth
72 x 72 x 49.2 (mm)
Standards
Standards
BS 89, UNE-EN 60051, IEC 144, UL94, DIN 43780, IEC 51, UNE 21318
Certifications
UL
Electrical safety, Maximum height (m)
2000

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Diagram connection
Datasheet
CE-certified

ACCESORIES