RS-485 / RS-232 Converter

RS2RS

RS2RS, Converter RS-232/RS-485 converter and RS-485/RS-485 amplifier,

Code: M62141.

    INFORMATION

    Description

    The RS2RS converter lets you connect units with RS-232 communications to a RS-485 network. It also works as a repeater or amplifier of RS-485 networks. The converter is designed to be used in industrial environments, thanks to its galvanic insulation.It automatically adapts to all half-duplex communications protocols without the need to modify the software. It works as a communications transducer between RS-232/RS-485 data buses or as an octocoupled RS-485/RS-485 amplifier. The RS2RS automatically switches between transmission (Tx) and reception (Rx) when it detects activity in the Tx transmission line, avoiding the need for software control.

    Using the RS2RS as an amplifier extends the length of an installation’s RS-485 bus, which generally does not exceed 1,200 metres. It can be used in installations where there are communication issues due to interference or cabling distances. The key features of the RS2RS converter are:

    • RS-232 / RS-485 bus transducer.
    • RS-485 / RS-485 amplifier.
    • Auto-detection of word speed and length, from 300 to 115,000 bauds.
    • Galvanic insulation, up to 3 kV.
    • 120 … 230 Vac power supply
    • Power, TX and RX LED
    • Assembly. DIN 46277 (EN-50022), 3 DIN 43880 modules

    Applications

    • For any installation that has units with RS-485 communications that need to communicate over an RS-232 connection.
    • Amplification of the RS-485 bus where the required distance exceeds 1200 metres.
    • Amplification of RS-485 signals in installations where there are communications problems.

    SPECIFICATIONS

    AC power supply
    Nominal voltage
    120 … 230 V ~ ± 10 %
    Frequency
    50 / 60
    Consumption
    0,7 … 2,3 VA
    Serial communication
    Technology / Type
    RS-232 / RS-485
    User interface
    LED
    3 LED ( Indication transmission : Tx and Rx - Power supply)
    Environmental characteristics
    Working temperature
    0 … +50 °C
    Storage temperature
    -10 … +60 ºC
    Relative humidity (without condensation)
    25 … 85 %
    Protection class
    IP 20
    Mechanical characteristics
    Envelope
    Noryl V0 1550
    Weight (kg)
    0,18
    Size (mm) width x height x depth
    70 x 106 x 58 (mm)
    Standards
    Standards
    UNE-EN 61000-6-2, UNE-EN 61000-6-4
    Electrical safety, Installation category
    CAT III 300 V (IEC 61010)
    Electrical safety, Maximum height (m)
    2000
    Electrical safety
    Insulation
    Double-insulated electric shock protection class II (IEC 61010-1)

    DIMENSIONS

    CONNECTIONS

    VIDEOS

    DOWNLOADS

    Technical guide
    Diagram connection
    Datasheet
    Software & Firmware