Slot harmonics in power generation systems

admin | 21 de October de 2015

 

Introduction

Technicians and engineers are broadly familiar with problems caused by lack of power quality and, more specifically, harmonics.

Filtration systems reduce and mitigate the actual harmonic current consumed by the receivers but, what if the source of the power quality is the generation system?

In this article we will look at slot harmonics, and a case study of resonance with these types of harmonics that are generated.

Slot harmonics

The actual construction of the stator windings of alternating current rotating electric machines can give rise to the appearance of harmonic components in voltage known as "slot harmonics". 

The existence of uniform slots around the internal part of the stator causes regular variations of reluctance and flux over the stator surface, producing distortion of the voltage wave.

Stator with slotsInduction Motor Elements

Slot harmonics occur at frequencies determined by the space between adjacent slots. The order of the components is expressed as follows:

FN-armonicos-ranura-formula1-en

where:

υslot = order of harmonic component
S = number of stator slots
P = number of machine poles
M = whole number, normally equal to 1, with which the lowest frequency slot harmonics are produced

The main effects of slot harmonics are:

Slot harmonic resonance

In this case the industry in question has a dual power supply, consisting of a 6.5 MW, 4.16 kV/60 Hz generator and direct power supply from the electrical network through a 69 kV primary electrical network with a 9 MVA transformer and 4.16 kV/60 Hz secondary. The installation had a motor control system (SMC), which was compensated with a 50 kvar, 4.16 kV capacitor.

Simplified diagram of the electrical system and electrical measurements

problems Problems

The installation had the following problems:

Tests Tests

4 different tests were carried out to the motor power supply:

  • Powered from the electrical network with and without a capacitor bank.
  • Powered from the generator with and without a capacitor bank.

Table 1 summarises the main electrical parameters measured, showing that the variation of the harmonic components without (Fig. 1 and 2) or with (Fig. 3 and 4) a capacitor bank is practically the same, having at all times the correct levels.

Table 1

Table 1

FN-armonicos-ranura-fig1-4-en

Table 2 shows the performance of the system powered by the 6.5 MW generator.There is a considerable increase in the voltage distortion when the 50 kvar capacitor is connected; the increase is mainly produced in the 37th order harmonic.

Table 2

Table 2

Fig5-8

Detail of the rotor and the stator in a generator

As figures 6 and 7 without a capacitor and figures 5 and 8 with a capacity show, the harmonic distortion operating with the generator is greater compared to the distortion produced operating directly with the electrical network; the 5th and 37th order components have apparently negligible amplitudes (1.89% and 1.26% respectively).

With the capacitor bank operating, there is resonance in the 37th harmonic with its amplitude at high values (>3%).

There were failures during the test, including the false alarm in the boiler control because of voltage distortion in all the circuits powered by the generator.

This resonance is caused by the combination of short-circuit parameters in the 4.16 kV, 71230 kVA DC bus, and the size of the capacitor, 50 kVAr. The tuning frequency is expressed as follows:

Formula

where:

 n = harmonic order of resonance
Scc = Short-circuit power available in the connection point of the capacitor bank
Q = Effective power of the capacitor bank

therefore:

Formula

Fig.9

FN-armonicos-ranura-fig9-en

We also saw that the generator was 4-pole and had 72 slots in its stator, so by applying the initial formula its lowest order slot harmonics are 35 and 37, coinciding with the resonance produced in the installation, and which entailed the various underlying problems. (Fig. 9)

An interesting aspect of this test was the fact that as the load dropped to 0, the distortion of the voltage wave increased, as shown in the figure with the profile of the voltage distortion rate THD(U)%.

Conclusions

picture conclusionsIn this case, the immediate measure was to leave the 50 kVAr capacitor permanently out of service, and to consider the need to use a capacitor bank with a detuned filter, detuned to 7%. However, the presence of the 37th voltage harmonic, being a generator design flaw, cannot be eliminated, meaning that in low load periods the same false alarm was produced in the boiler control. It was therefore suggested that power should be provided through an online type UPS system in order to eliminate this component from the power supply voltage.

It is becoming more essential to use compensation units with detuned filters due to the increase in applications with electronic and power electronic devices, whose effects these days cannot be discounted.

The deployment of a monitoring system enables the diagnosis, control and efficient use of electrical energy, and to help detect any anomaly in our installation.

 

Click here to download this article in PDF pdf format: es  en  de  fr  pl  pt

 

You can read our news in the news section.
You can also follow our publications on CIRCUTOR's Twitter account, and on LinkedIn.

WRITTEN BY CIRCUTOR

SHARE THIS ARTICLE

NEWSLETTER