Many times we find the question that how many reactive power to be compensated must be chosen after making a measurement with a network analyzer. This situation is crucial in determining proper reactive compensation system in MV.
The presence of harmonics in the electrical system may also influence considerably, not only upon the operation of the capacitor bank, but the entire system power quality.
This article will explain how to define the power and steps that power factor correction in MV should be, using a simple statistical method, and assess risks to the presence of harmonics in the electrical system.
We must start any analysis of reactive power compensation with a measure carried out with a network analyzer (CIR-e3, AR5L or AR6), where we record the consumption of reactive power to compensate of the installation.
We should proceed according to the following principles so that a correct data logging is achieved for further accurate analysis:
After obtaining the data, we must analyze them. We will use a very simple but yet very useful statistical method such as histograms.
A histogram is a graphical representation of a frequency distribution given values. The distribution of values is divided into intervals. These intervals could be selected as one decides, but too short or too large intervals could be impossible to analyze.
One method to determinate the optimal interval size is with the following formula [1.1]:
XMAX is the maximum value, XMIN is the minimum value, and k is the number of intervals calculated according to the Velleman method, k = 2·N1/2, where N is the number of values. To avoid deviations you can delete outliers that could affect the correct approach.
Let we go through an example of analysis using reactive power histogram. We can observe the three-phase inductive reactive power consumption at a voltage of 6,6 kV in an industry, where they are paying penalties for low power factor, in Figure 1.
By applying formula [1.1], the proposed interval value that is got would be:
Anyway, since usually, M.V. automatic capacitor banks are based on 100 kvar multiples, in this case we choose this interval of 100 kvar, which will better suit to the compensation requirements of this installation. Thus, the result of applying this interval is the histogram of Figure 2.
As you can see from the results, most of the consumption of reactive power is 1400 kvar, followed of 1000 kvar and 500 kvar. Therefore, with a configuration of steps will be 1x500 and 1x1000 kvar.
In this way, we can choose an optimized configuration of the capacitor bank that we could compensate the installation more than 98% of the time.
Obviously this method allows us to determine the steps to form the capacitor bank, but we must not forget other factors that may influence the selection of the capacitor bank.
The presence of harmonics can affect the performance of the equipment and the power quality of the entire installation.
When we carry out inductive reactive power compensation, the incorporation of a parallel capacitor bank is logical to attenuate this demand in order to bring the demanded apparent power (kVA) nearest to the active power (kW), which is really used to carry out to the purpose it is designed for. This simple concept can be summarized as a parallel circuit with inductance (L – Transformer and Grid) and capacity (C – Capacitor bank).
If we observe the frequency response of the system, we see that for a frequency fR the impedance of the system is much greater than its normal performance.
The existence of current with frequencies higher than the fundamental frequency at 50 or 60 Hz, mean that the resonance conditions could be complied with. This would basically cause:
There are two methods to check or detect the risk of resonance. First method is to calculate the frequency of resonance with the following formula:
Where SSC is the short-circuit power of the power transformer (kVA), Q is the reactive power of the capacitor bank (kvar) and f is the rated frequency of the system (50 or 60 Hz).
Then you can check if the frequency of resonance could be close or not to harmonic current presence in the installation, therefore could produce a resonance between the capacitor bank and the network.
The second method is to detect if the capacitor bank is producing or not a parallel resonance with a measurement. We just need to take measurements with and without the capacitor bank connected, and see the performance of THDU%.
If the THDU% increases so much when you connect the capacitor bank, it will means that exists an important resonance and it will damage the capacitor bank, as well as, the whole equipment connected in that installation.
The only way to avoid this risk of resonance is to install a detuned capacitor bank that reject the parallel resonance this the most common harmonics presence in the installation.
A brief summary of this paper may conclude that the right choice of a capacitor bank to compensate any M.V. must take into account two essential points: