Three-phase static switching units for 3-terminal capacitors

EMB-2PH-50-400

EMB-2PH-50-400, Static switching

Code: R41323.

  • kvar (230 V): 27,5
  • kvar (400 V): 50

INFORMATION

Description

EMB-2PH static switching modules series are the building blocks for the construction of static capacitor banks for Power Factor Correction.

These capacitor banks use thyristors instead of the classic contactors for the connection of each capacitor stage and they are ideal in installations with fast and large load fluctuations (load changes from tents of seconds up to 8 or 10 seconds).

Applications

EMB-2PH static switching modules have been designed to connect and disconnect capacitors in some milliseconds. They can be used to build capacitors with some stages, or for the individual compensation of a load that must be compensated instantly and which is not able to be disconnected such as welding machines, cranes, lifts, etc.

SPECIFICATIONS

AC power supply
Frequency
50/60 Hz
Electrical characteristics
Voltage
Up to 3 x 440 V~ (without detuned filters) Up to 3 x 415 V~ (with detuned filters)
Maximum transient current
1.5 In for 1 min
Environmental characteristics
Working temperature
80 ºC max. heatsink temperature
Ambient temperature
45 ºC (máx)
Protection class
IP 00
Mechanical characteristics
Ventilation
Fan: auxiliary voltage at 1x230 V~ (at terminals A1, A2)
Weight (kg)
5,9
Size (mm) width x height x depth
200 x 220 x 200 (mm)
Protection
Element
Fuses not included. External protection against overload and short circuits is required. 90°C thermostat
du / dt
RC protection at 1000 V/µs
di / dt
100 A/µs (L = 12 µH, not included, must be assembled in series with the condenser)
Standards
Standards
IEC 61439

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Dimensions
Datasheet

ACCESORIES