Power analyzer, panel mounted 96x96

CVM-C4-ITF-485-ICT2

CVM-C4-ITF-485-ICT2, Power analizer, panel mounted 96x96

Code: M52706.

  • Protocol: Modbus/RTU
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Measuring current Channels: 3
  • Input current: .../5 A | .../1 A
  • Mounting: Pannel

INFORMATION

Description

CVM-C4 is a power analyser that measures, calculates and displays the main electrical parameters for single-phase and three-phase networks (with or without neutral) on its screen. Measurement is made in true rms value, by means of 3 AC voltage inputs and 3 /5 A or /1 A current inputs. Relay outputs enable local operation in the event of an alarm event being triggered. Its dimensions are 96 x 96 mm with a depth of only 41.5 mm. Current measurement is indirectly carried out by /5A or /1A transformers. It allows AC (80...270 Vac)and DC (80...270 Vdc or 18... 36 Vdc power supply systems). It features RS-485 communications enabling remote data readout or Scada or Master centralisation.

Applications

  • For electrical parameter measurement in areas whose reduced dimensions require the installation of a space-saving panel analyser.
  • Instantaneous value measurement of electrical parameters with communications.
  • Logging of consumed or generated Active or Reactive Energy.
  • The device's relay outputs allow the installation to be locally operated.
  • Programmable alarms by setting relay activation time, connection delay and hysteresis.
  • 5000 imp/kWh energy impulse outputs
  • Energy measurement of two different sources on 2 separate meters (by digital input activation).
  • Voltage and current THD% measurement to check for harmonics in the installation.

SPECIFICATIONS

AC power supply
Installation category
CAT III 300 V
Consumption
6 … 18 VA
Frequency
50/60 Hz
Nominal voltage
80 ... 270 Vac
DC power supply
Installation category
CAT III 300 V
Consumption
1.5 ... 1.8 W
Nominal voltage
80…270 Vdc
Mechanical characteristics
Size (mm) width x height x depth
96 x 96 x 41.5 (mm)
Envelope
Polycarbonate + ABS
Torque setting
0.5 Nm
Communications cable cross-section
2.5 mm2
Cable gauge at power supply terminals
2.5 mm2
Cable gauge at input and output terminals
2,5 mm 2
Cable gauge at current terminals
2,5 mm2
Cable gauge at voltage terminals
2.5 mm2
Weight (kg)
0,268
Environmental characteristics
Protection class
Front: IP54, Rear: IP20
Relative humidity (without condensation)
5 … 95%
Storage temperature
-20 … +70 ºC
Working temperature
-10 … +60 ºC
Current measurement circuit
Installation category
CAT III 300 V
Consumption
< 0.2 VA (por fase)
Nominal current (In)
1 A / 5 A ~
Allowable overload
1.2 In continuous, 10 In instantaneous(5s)
Voltage measurement circuit
Installation category
CAT III 300 V
Consumption
< 0.2 VA (por fase)
Sampling frequency
45…65 Hz
Input impedance
> 1.7 MΩ
Voltage measuring range
45…65 Hz
Nominal voltage
100…277 V~ Ph-N (± 8%)
Maximum permanent measurement voltage
1.2 Un continuous, 2 Un instantaneous (1 min)
Minimum measurement voltage (Vstart)
10 V
Communications
Data bits
8
Stop bits (ModBus)
1-2
Parity
without, even, odd
Protocol
ModBus RTU
Speed
2400-4800-9600-19200
Standards
Electrical safety, Maximum height (m)
2000
Electrical safety, Installation category
CAT III 300 V
Electrical safety, Contamination level/class
Pollution resistance 2
Standards
IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
User interface
Keyboard
3 keys
Display type
LCD
Digital inputs
Input/output insulation
3,75 kV RMS
Quantity
2
Type
Potential-free contact
Maximum short-circuit current
4 mA
Maximum open circuit voltage
30 V
Digital relay outputs
Quantity
2
Type
Relay
Resistive load (max.)
250 Vca / 5 Aca, 30 Vcc / 5 Acc
Maximum current
5 A ~
Maximum open contact voltage
277 V ~ / 30 Vdc
Electrical life
(250 V ~ / 5 A) 1 x 105
Maximum switching capacity
1385 VA / 150 W
Digital transistor outputs
Pulse width
Minimum pulse width: 80mA
Type
Passive impulse
Maximum frequency
10 Hz
Maximum current
27 mA
Maximum voltage
27 Vcc
Measurement accuracy
Frequency measurement
0.5 %
Phase current measurement
0.2 %
Reactive energy measurement (kvarh)
0.5 %
Reactive power measurement (kvar)
0.5 %
Active energy measurement (kWh)
0.5 %
Active power measurement (kW)
0.5 %
Phase voltage measurement
0.2 %

DIMENSIÓN

VÍDEOS

DESCARGAS

User's manual
Technical guide
Dimensions
Diagram connection
Datasheet
Catalogue
CE-certified
Other Certificates
Software & Firmware

ACCESORIOS