Current transformers, split core

STP-24 100/1A

STP-24 100/1A, Split core current transformer

Code: M733230010000

  • Inner diameter (mm): 24
  • System: Single-phase
  • Class 3 Power (VA): 1
  • Measurement Range (A): 100/1
  • Input current: 100 A
  • Power (VA): 1
  • Transformer type: Split core

INFORMATION

Description

Open-core current transformers with compact dimensions for easy installation. This type of transformer is very easy to install and uninstall on compact panels where the reduced space makes it difficult to take current measurements. In addition, their open-core design means that they can take measurements without having to interrupt the electric supply. The primary current measurement range is from 100 A to 300 A using different secondary outputs (.../1A, .../5A or .../250mA) with a maximum admissible cable diameter of 24 mm.

Applications

Quick and easy assembly are a fundamental aspect when taking temporary measurements in an electrical installation. STP-24 transformers can take energy measurements together with CIRCUTOR's power analyzers or energy meters (CVM-MINI, CVM-NET, CVM-C, CVM-B, EDMk, etc.) without having to interrupt the electric supply. The open-core design of the transformer makes it very easy to install and allows installers to take electrical measurements in less time.

SPECIFICATIONS

Electrical characteristics
Safety factor (SF)
2.5
Power
1 VA (Class 3)
Insulation voltage between terminals S1-S2
3 kV 1 min
Mechanical characteristics
Size (mm) width x height x depth
66 x 76 x 55 (mm)
Envelope
Plastic V0 self-extinguishing (UNE 21031)
Weight (kg)
0,23
Environmental characteristics
Thermal Class
class B (+130 ºC)
Relative humidity (without condensation)
15 … 85%
Storage temperature
-40 … +85 ºC
Working temperature
-20 … +55 ºC
Specific technical characteristics of current sensors
Inner diameter Ø (mm)
24
Operating voltage
0,72 kV~ máx.
Current measurement circuit
Nominal frequency
50 / 60 Hz
Primary current measurement
100 A
Allowable overload
1,2 x In
Dynamic current (Idyn)
2,5 Ith
Thermal short-circuit current (Ith)
60 In
Minimum current measurement
0,01 x In
Transformation ratio
… / 1 A
Standards
Standards
IEC 60044-1, IEC 61010-1
Measurement accuracy
Accuracy
Clase 3

DIMENSIONS

CONNECTIONS

VIDEOS

DOWNLOADS

Datasheet
CE-certified

ACCESORIES